6.2.4 TIMING
6.2.4 TIMING6.2.4 TIMING
6.2.4 TIMING
Timing is active both with systems with pressure switches and with systems with sensors.
Phase
Display Comment Field Default
0
00
0
TIMING
TIMINGTIMING
TIMING
1 P1 START DELAY
Delay in starting P1 (jockey included).
The time count begins from the start
request from the pressure switch/sensor.
0..100 s 3 s
2 P2-3 START DELAY
Delay in starting P2 - P3. The time count
begins from the start request from the
pressure switch/sensor.
0..100 s 5 s
3 P1 STOP DELAY Delay in stopping P1 (jockey included).
The time count begins from the stop
request from the pressure switch/sensor.
0..100 s 5 s
4 P2-3 STOP DELAY
Delay in stopping pumps P2 - P3. The
time begins from the stop request from
the pressure switch/sensor.
0..100 s 3 s
5 DYNAMIC TIMES Settable only on system with sensor.
Halves the times previously set in the
case of excessive variation of the
pressure/level/etc. of the system.
YES
NO
NO
6.2.5 PERIODIC AUTO TEST
6.2.5 PERIODIC AUTO TEST6.2.5 PERIODIC AUTO TEST
6.2.5 PERIODIC AUTO TEST-
--
-RUN
RUNRUN
RUN
In systems subject to long periods of inactivity it is recommended to perform a periodic automatic test
(auto test-run) with the aim of checking the performances of the group.
In any case the autotest cannot replace programmed maintenance, which must be carried out
periodically. A weekly interval is recommended.
To start the test request the board’s internal clock may be used, or an external command. When autotest
is enabled, the alarm relay is automatically configured to control the solenoid valve.
It is also necessary to ensure that the parameter CONFIG. IN. AUX3 in the DIGITAL IN/OUT MENU is set as
CONV.L.SWITCH (Minimun Pressure Switch).
Phase
Display Comment Field Default
0
00
0
AUTO
AUTOAUTO
AUTO-
--
-TEST
TESTTEST
TEST RUN
RUN RUN
RUN
1 AUTO TEST REQ. Autotest command source.
The possible settings are:
Disabled: autotest is inhibited.
Internal clock: autotest is activated on
the day and time requested from the
SM30 BSETF3 board by the internal
clock.
Ext. command: autotest is activated by
the external command connected to the
digital input AUX1
DISABLED
INTERNAL
CLOCK
EXT.ON /OFF
DISABLED