
30
Entering compensation values: (system curve)
For steps 1 through 4, refer to the flow chart.
Instructions
1. From the main menu, hold down the key
for 2-3 seconds until the display changes to:
•Enter66 by pressing the
2. Freq.- Lifting 30.0 hz
This indicates the speed (flow rate)
at which you want the pressure compensation to begin. On a
60 hz system, there is virtually no flow below 40 hz. Set this
frequency with the up arrow. On a 50 hz system, the normal
starting point would be 30 hz.
•Usethe keytoscrollthroughthe
menu screens until you reach:
Change if required.
3. Use the key to move to the next screen:
•Usethe toenterthepercentage
pressure increase calculated on page 29.
Increase values are recommended from 0
to 20%. If your friction loss increase is above 20% of your set pressure, please contact
the AQUAVAR distributor or factory for application assistance. 0-99.9% actual.
4. Save the new settings.
•Usethe keytoscrolltothescreen
•Pressboththearrows until the display
indicates the save process is complete.
The screen will automatically return to the main menu.
Programming
Screen
FREQ - LIFTING 40.0 HZ
LIFT - INTENS. 0.0%
LIFT - INTENS. 3.0%
SAVE ??? +
SAVE ??? SAVED
t
t
t
t
t
t
t
*
*
*
*
PASSWORD 0000
0066
Comentarios a estos manuales