SECTION 6: POWER SUPPLY AND WIRING (CONTINUED)
POWER CONNECTION DIAGRAMS
The following diagrams show the power connection layout for each frame size.
• For sizes R5 and N5 • For sizes R6 and N6
WARNING
If the secondary of the transformer is a delta with a grounded leg (corner grounded delta) or
oating network, the line to ground EMC lter components and line to ground MOV protection
must be disconnected or damage to the controller can result. Remove screws F1 and F2 for
frame sizes R5/N5 and R6/N6 to disable line to ground EMC lter and MOV protection.
NOTE
For single phase input power, use input power terminals U1, W1 and PE (ground).
WARNING
Hazardous
voltage
FIGURE 2
FIGURE 3