4XXXX REGISTER MAPPING
DRIVE PARAMETERS
Modbus Ref. Contents R/W Remarks
40002 Reference 1 R/W
Use for Speed Control Macro Only
Range = 0 … 10000 (0 … 100.00%)
40003 Reference 2 (Setpoint) R/W
Remote Setpoint via Modbus
Range = 0 … 10000 (0 … 100.00%) of Transducer range.
e.g. 0 = 0 psi and 10000 = 300 PSI.
NOTE: Group 16 Setpoint Select must be set to Fieldbus
40005
Actual 1
(Select using 3210)
R
By default, stores nothing. Use parameter 3210 to
select an actual value for this register.
e.g. 3210 = 0101, 40006 = Motor Freq.
40006
Actual 2
(Select using 3211)
R
By default, stores nothing. Use parameter 3211 to
select an actual value for this register.
40007
Actual 3
(Select using 3213)
R
By default, stores nothing. Use parameter 3213 to
select an actual value for this register.
40008
Actual 4
(Select using 3214)
R
By default, stores nothing. Use parameter 3214 to
select an actual value for this register.
40009
Actual 5
(Select using 3214)
R
By default, stores nothing. Use parameter 3215 to
select an actual value for this register.
40010
Actual 6
(Select using 3214)
R
By default, stores nothing. Use parameter 3216 to
select an actual value for this register.
40011
Actual 7
(Select using 3214)
R
By default, stores nothing. Use parameter 3217 to
select an actual value for this register.
40012
Actual 8
(Select using 3214)
R
By default, stores nothing. Use parameter 3218 to
select an actual value for this register.
40031 Aquavar Control Word LSW R/W
Maps directly to the Least Significant Word of the
Aquavar profile’s CONTROL WORD.
40032 Aquavar Control Word MSW R
Maps directly to the Most Significant Word of the
Aquavar profile’s CONTROL WORD.
40033 Aquavar Status Word LSW R
Maps directly to the Least Significant Word of the
Aquavar profile’s STATUS WORD.
40034 Aquavar Status Word MSW R
Maps directly to the Most Significant Word of the
Aquavar profile’s STATUS WORD.
Group 1 VFD Signal R/W Set Value (Dec)
40101 Motor Frequency R
40102 Motor Current R
40103 Motor Power R
40104 DC Bus Voltage R
40105 Motor Voltage R
40106 Drive Temp R
40107 VFD On Time R
40108 Run Time R
40109 KWh Counter R
40110 DI6-1 Status R
40111 AI1 R
40112 AI2 Trnsdcr Fdbk R
40113 RO3-1 Status R
40114 AO1 (mA) R
40115 AO2 (mA) R
40116 Last Fault R
40117 Previous Fault 1 R
40118 Previous Fault 2 R