4XXXX REGISTER MAPPING
DRIVE PARAMETERS
Group 10 VFD Signal R/W Set Value (Dec)
41001 Parameter Lock R/W Locked [0], Open [1]
41002 Pass Code R/W
41003 Local Lock R/W Off [0], On [1]
41004 Parameter Save R/W Done [0], Save… [1]
41005 New Pass Code R/W
41006 Set Point Lock R/W Off [0], On [1]
Group 11 VFD Signal R/W Set Value (Dec)
41101 Language R/W
English [0]
Espanol [1]
Francais [2]
41102 Application Macro R/W
Single Pump [1]
Synchronous [2]
Multicontrol [3]
Constant Slv [4]
Speed Contrl [5]
41103 Motor Nom Voltage R/W
41104 Motor Nom Current R/W
41105 Motor Nom Freq R/W
41106 Motor Nom RPM R/W
41107 Motor Nominal Power R/W
Group 12 VFD Signal R/W Set Value (Dec)
41201 Start/Stop R/W
Keypad [0]
Fieldbus [1]
41202 Auto Restart R/W On [0], Off [1]
41203 Test Run R/W
Not Sel [0]
Auto [1]
Manual [2]
41204 Test Speed % (FL) R/W
41205 Test Run Delay R/W
41206 Motor Jog R/W
Disable [0]
Jog [1]
Group 13 VFD Signal R/W Set Value (Dec)
41301 Ramp1 Fast Accel R/W
41302 Ramp2 Fast Decel R/W
41303 Ramp3 Slow Accel R/W
41304 Ramp4 Slow Decel R/W
41305 Ramp Hysteresis R/W
41306 Reg Window R/W