1XXXX MAPPING - MODBUS DISCRETE INPUTS / AQUAVAR STATUS WORD
Modbus Ref. Internal Location R/W Indication Value
10001 Status Word - Bit 0 R READY
1 = READY,
0 = NOT READY
10002 Status Word - Bit 1 R ENABLED
1 = ENABLED,
0 = NOT ENABLED
10003 Status Word - Bit 2 R STARTED
1= STARTED,
0 = NOT STARTED
10004 Status Word - Bit 3 R Reserved (Not Used)
10005 Status Word - Bit 4 R ZERO_SPEED
1 = 0 Hz,
0 = > 0 Hz
10006 Status Word - Bit 5 R ACCELERATE
1 = ACCELERATING,
0 = NOT ACCELERATING
10007 Status Word - Bit 6 R DECELERATE
1 = DECELERATING,
0 = NOT DECELERATING
10008 Status Word - Bit 7 R AT_SPEED
1 = MAX FREQUENCY,
0 = NOT MAX FREQUENCY
10009 Status Word - Bit 8 R Reserved (Not Used)
10010 Status Word - Bit 9 R Reserved (Not Used)
10011 Status Word - Bit 10 R Reserved (Not Used)
10012 Status Word - Bit 11 R Reserved (Not Used)
10013 Status Word - Bit 12 R PANEL_LOCAL
0 = NOT LOCAL
1 = LOCAL
10014 Status Word - Bit 13 R Reserved (Not Used)
10015 Status Word - Bit 14 R EXT2_ACT
0 =Speed Control Mode
1 = All Other Macros
10016 Status Word - Bit 15 R FAULT
0 = NO FAULT,
1 = FAULT
10017 Status Word - Bit 16 R ALARM
0 = NO ALARM,
1 = ALARM
10018 Status Word - Bit 17 R REQ_MAINT
10019 Status Word - Bit 18 R Reserved (Not Used)
10020 Status Word - Bit 19 R LOCAL LOCK
0 = LOCAL LOCK OFF,
1 = LOCAL LOCK ON
10021 Status Word - Bit 20 R Reserved (Not Used)
10022 Status Word - Bit 21 R Reserved (Not Used)
10023 Status Word - Bit 22 R Reserved (Not Used)
10024 Status Word - Bit 23 R Reserved (Not Used)
10025 Status Word - Bit 24 R Reserved (Not Used)
10026 Status Word - Bit 25 R Reserved (Not Used)
10027 Status Word - Bit 26 R Reserved (Not Used)
10028 Status Word - Bit 27 R Reserved (Not Used)
10029 Status Word - Bit 28 R Reserved (Not Used)
10030 Status Word - Bit 29 R Reserved (Not Used)
10031 Status Word - Bit 30 R Reserved (Not Used)
10032 Status Word - Bit 31 R Reserved (Not Used)
10033 DI1 R DI1 0 = OFF, 1 = ON
10034 DI2 R DI2 0 = OFF, 1 = ON
10035 DI3 R DI3 0 = OFF, 1 = ON
10036 DI4 R DI4 0 = OFF, 1 = ON
10037 DI5 R DI5 0 = OFF, 1 = ON
10038 DI6 R DI6 0 = OFF, 1 = ON